CN606  Six Zone Temperature Monitors

with HI /LO Alarms AC Models

 

CN606TC1

CN606RTD2

CN606RTD3

Description

The CN606 Series is a microprocessor based scanner

 which accepts signals from thermocouples or RTD's.

In the basic unit, six  zones are sequentially scanned

with a selectable display rate of 1 to 40 seconds each.

A single output relay is provided to indicate an alarm

condition on any zone. The  faceplate has been

arranged to call attention to an alarm condition

by flashing the main temperature display and indicating

 the zone in alarm with a flashing zone number display.

To prevent alarm on startup,  Lo alarm is not activated

until  enabled  zones cross Lo alarm setpoint.

The CN606 Series implements a security password

to protect certain functions.

 

 

Available for purchase on line: CN606

 CN606 Six Zone Temperature Monitors

with HI /LO Alarms DC Models

 

CN606TC1-DC

CN606RTD2-DC

CN606RTD3-DC

 

SPECIFICATIONS

No. of Zones                 Six      

Zone Display Time       1-40 seconds

Scan Time                    Approx. 1/4 sec

Accuracy                      ±0.2% Range  ±2 °C

Resolution                    ±5uV

Linearity                      ±1 °C

Scale Selectable            °C or °F

Open Input Warning     Flashing Display

Alarm Relay                 5 Amp; 120VAC

Relay                            deenergizes on alarm

Communication            RS232 (3wire)

Alarms Selectable         HI, LO, HI/LO

Alarm Range                Full Range

Terminals                     Headers for Plug-in Wiring

Enclosure                     1/4 Din Aluminum 6"long

Reset                            Manual

Main Display                Four Digit; 0.6" high

 

Max. Voltage between

Inputs                          6VDC or RMS

On Power Loss             Unit saves settings

Automatic  Cold Junction Compensation         

 

Line PowerAC Model    120/240VAC; 50/60Hz

Power Consumption     10VA Max.

           

Line Power DC Model 9 - 36 VDC

                       

T/C Model

Thermocouple Type                  J,K,E,T,S,R,B,C

                                         

RTD Model

RTD  (2 or 3 wire)                    Pl, Ni, Cu